Dimensions and electrical data

Cross Section 3×2,5 3×4 3×6 3×10 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150
Phase and Earth Conductors |
Number and cross section mm2 3×2,5 3×4 3×6 3×10 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150
Insulation thickness mm 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 2.0 2.2 2.3
Cable details |
Radial thickness of inner sheath mm 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.8 3.8 5.0
Size of armour mm 7/0,45 7/0,45 7/0,71 7/0,71 7/0,71 7/0,90 7/0,90 7/0,90 7/0,90 7/0,90 7/0,90 7/1,25
Outer sheath thickness mm 2.5 2.5 3.8 3.8 3.8 4.0 4.3 4.7 5.2 5.8 6.2 6.6
Min. overall diameter mm 24.5 25.8 34.3 36.2 38.6 43.6 46.6 51.3 56.6 68.4 72.2 83.3
Max. overall diameter mm 26.9 28.2 36.5 38.4 40.8 47.0 50.6 56.7 62.7 72.1 77.0 87.3
Min. bending radius mm 243 254 329 346 368 423 456 511 565 649 693 786
Appx. cable weight kg/km 990 1.15 2 2.35 2.75 3.35 4.3 5.32 6.75 8.75 10.65 12.5
Copper weight kg/km 72 115 173 288 461 720 1.008 1.44 2.016 2.736 3.456 4.32
Electrical details
“Continuous current | rating at 25°C Ambient” A 28 37 46 63 85 110 135 170 205 250 295 320
Max. DC resistance at 20°C
Phase and earth conductors Ω /km 8.21 5.09 3.39 1.95 1.24 0.795 0.565 0.393 0.277 0.210 0.164 0.132
Armour Ω /km 4.6 4.2 2.2 2.0 1.9 1.3 1.2 1.1 0.94 0.80 0.74 0.45

Manufactured by Üntel Kablo. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for cross-section, drum length, certification and lead time.