Skip to product information
Üntel BS 6708 TYPE 307S

Üntel BS 6708 TYPE 307S

Ships within 3–5 business days, subject to prior ex-stock sales.

Technical support available

Custom lengths available on request

SS & IEC certified products

BS 6708 TYPE 307S — Üntel Kablo cable for mining applications.

Dimensions and electrical data

Cross Section 3×50+35+3×4 3×70+50+3×6 3×95+50+3×6 3×120+70+3×10
Phase Conductor
Number and cross section mm2 3×50 3×70 3×95 3×120
Insulation diameter Nom. mm 15.80 17.80 19.20 21.60
Screen diameter Nom. mm 18.20 20.15 21.60 23.95
Earth Conductor
Number and cross section mm2 1×35 1×50 1×50 1×70
Stranding mm 276/0,40 396/0,40 396/0,40 360/0,50
Conductor diameter Nom. mm 8.20 9.80 9.80 11.70
Pilot Conductor
Number and cross section mm2 3×4 3×6 3×6 3×10
Stranding mm 56/0,30 84/0,30 84/0,30 80/0,40
Conductor diameter Nom. mm 2.60 3.50 3.50 4.40
Insulation diameter Nom. mm 5.55 6.40 6.40 7.30
Diameter over sheath Nom. mm 17.80 19.80 21.20 23.60
Cable details
Min. overall diameter mm 56.8 62.8 68.9 73.4
Max. overall diameter mm 59.8 65.8 72.7 77.2
Min. bending radius mm 478 526 581 617
Max. pulling tension kgf 1.2 1.68 2 2
Appx. cable weight kg/km 5.85 7.15 8.6 10.5
Copper weight kg/km 2.685 3.319 4.039 4.951
Electrical details
“Continuous current | rating at 25°C Ambient” A 170 205 250 295
“Intermittent current | rating at 25°C Ambient” A 210 255 315 360
Max. DC resistance at 20°C
Phase Conductor Ω /km 0.393 0.277 0.21 0.164
Pilot Conductor Ω /km 5.09 3.39 3.39 1.95
3 screens and earth in | parallel connection Ω /km 0.35 0.35 0.28 0.28
Nom. reactance at 50Hz Ω /km 0.113 0.108 0.105 0.101
Nom. reactance at 60Hz Ω /km 0.136 0.129 0.126 0.121
Min. insulation | resistance at 20°C M Ω /km 950 820 720 660
3 phase voltage drop on full load current mV/A/m 0.85 0.61 0.48 0.39

Manufactured by Üntel Kablo. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for cross-section, drum length, certification and lead time.