BS 6708 TYPE 307 — Üntel Kablo cable for mining applications.

Dimensions and electrical data

Cross Section 3×25+25+16 3×35+25+16 3×50+35+25 3×70+50+35 3×95+50+50 3×120+70+70 3×150+70+95
Phase Conductor
Number and cross section mm2 3×25 3×35 3×50 3×70 3×95 3×120 3×150
Insulation diameter Nom. mm 13.10 14.70 15.70 17.70 19.10 21.40 23.00
Screen diameter Nom. mm 15.50 17.10 17.70 19.70 21.10 23.40 25.00
Earth Conductor
Number and cross section mm2 1×25 1×25 1×35 1×50 1×50 1×70 1×95
Stranding mm 196/0,40 196/0,40 276/0,40 396/0,40 396/0,40 360/0,50 475/0,50
Conductor diameter Nom. mm 7.00 7.00 8.50 10.00 10.00 11.70 13.50
Pilot Conductor
Number and cross section mm2 1×16 1×16 1×25 1×35 1×50 1×70 1×95
Stranding mm 126/0,40 126/0,40 196/0,40 276/0,40 396/0,40 360/0,50 475/0,50
Conductor diameter Nom. mm 5.50 5.50 7.00 8.50 10.00 11.70 1.35
Insulation diameter Nom. mm 11.60 11.60 13.10 14.70 15.70 17.70 19.10
Cable details
Min. overall diameter mm 47.4 51.6 56.8 62.8 68.9 73.4 75.9
Max. overall diameter mm 49.9 54.6 59.8 65.8 72.7 77.2 79.7
Min. bending radius mm 400 440 480 525 580 615 640
Max. pulling tension kgf 640 830 1.2 1.68 2 2 2
Appx. cable weight kg/km 4 4.8 6.15 7.6 9.25 11.2 13
Copper weight kg/km 1.654 1.948 2.666 3.482 4.346 5.45 6
Electrical details
Continuous current | rating at 25°C Ambient A 110 135 170 205 250 295 320
Intermittent current | rating at 25°C Ambient A 130 155 210 255 315 360 385
Max. DC resistance at 20°C
Phase Conductor Ω /km 0.795 0.565 0.393 0.277 0.21 0.164 0.132
Pilot Conductor Ω /km 1.24 1.24 0.795 0.565 0.393 0.277 0.21
3 screens and earth in parallel connection Ω /km 0.5 0.5 0.35 0.35 0.28 0.28 0.14
Nom. reactance at 50Hz Ω /km 0.125 0.117 0.113 0.108 0.105 0.101 0.098
Nom. reactance at 60Hz Ω /km 0.15 0.141 0.136 0.129 0.126 0.121 0.118
Min. insulation | resistance at 20°C M Ω /km 1250 1100 950 820 720 660 600
3 phase voltage drop on full load current mV/A/m 1.69 1.21 0.85 0.61 0.48 0.39 0.32

Manufactured by Üntel Kablo. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for cross-section, drum length, certification and lead time.