and Applications For applications in dry and damp places, inside buildings as well as outdoors, most of all for current supply, open installations, electricity distribution, industries and so on. The cable is resistant to abrasion, oils and fats and is flame retardant.

Construction
Phase Conductors
Conductor material: tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)
Insulation
Insulation material: 3GI3 quality rubber compound, according to VDE 0207 Part 20
Nominal thickness: According to VDE 0250 Part 812
Cores identification
According to VDE 0293 Part 308 (HD 308)
Individual core screen
Material: Bare copper
Construction: Copper braid up to 10 mm², copper wires from 16 mm²
Control conductors
Conductor material: tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)
Insulation material: 3GI3 quality rubber compound, according to VDE 0207 Part 20
Inner Sheath
Material: Rubber compound GM1b quality, according to VDE 0207 Part 21
Outer Sheath
Material: Rubber compound 5GM5 quality, according to VDE 0207 Part 21
Colour: Yellow
Electrical
Nominal rated voltage U₀/U (kV)
0,6/1
Test voltage (kV)
3
Max AC voltage (kV)
0,7/1,2
Max DC voltage (kV)
1,8
Current rating (A)
according to VDE 0298 Part 4
Thermal and mechanical
Maximum short circuit temperature (°C)
250
Maximum working temp. on the conductor (°C)
90
Ambient temperature: mobile condition (°C)
- 25 to + 80
Ambient temperature: static condition (°C)
- 40 to + 80
Bending radius (mm)
According to VDE 0298 Part 3
Submersible (m)
100
Maximum tensile load (N/mm²)
15
Note
Referred to the total phase conductors cross section
Resistance
Burning behaviour
Flame retardant according to IEC 60332-1-2
Resistance to oil
According to IEC 60811-2-1
Ozone resistance
According to IEC 60811-2-1
Behaviour in water
HD 22.16 and AC internal test, suitable for immersion in salt and brackish water
Weather resistance
For indoor and outdoor application
Standards and compliance
Flame retardant
IEC 60332-1-2
Source