Resources
Installation methods
How a cable is installed sets how much current it can carry. Find your installation to see its SS 638:2018 reference method.
Conduit C1–C2
-
Sheathed cables in conduit inside an insulated wall
- Conduit runs within a thermally insulating wall
- Conduit touches the inner wall lining on one side
SS 638 Table 4A, item 6
-
Cables in conduit set in masonry or concrete
- Brick, block, concrete or plaster
- Not thermal insulation
SS 638 Table 4A, item 7
Trunking K1–K3
-
Cables in trunking on a wall or suspended
- Surface trunking fixed to a wall, or hung clear of it
SS 638 Table 4A, item 8
-
Cables in flush floor trunking
- Trunking set into the floor screed, lid flush with the floor
SS 638 Table 4A, item 9
-
Single-core cables in skirting trunking
- Trunking run along the base of the wall
SS 638 Table 4A, item 10
Tray T1
-
Sheathed cables bunched on a perforated tray
- Holes make up at least 30% of the tray surface
- Cables touching, open to the air
SS 638 Table 4A, item 11
Free air F1–F3
-
Single-core cables spaced in free air
- Flat, vertical or horizontal: one overall diameter (Dₑ) between cables, at least 0.5 Dₑ from the wall
- Trefoil: at least 0.5 Dₑ from the wall to the nearest cable, or 0.75 Dₑ to the nearest cables
- Supports under the cables cover less than 10% of the plan area
SS 638 Table 4A, item 12
-
Multicore cables on ladder or brackets
- Cables more than 2 Dₑ apart
- At least 0.3 Dₑ from the wall
- Supports under the cables cover less than 10% of the plan area
SS 638 Table 4A, item 13
-
Cables hung from a catenary wire
- Supported by, or built around, a catenary wire
- Use Method 12 for single cores, 13 for multicores
SS 638 Table 4A, item 14
Building voids V1–V2
-
Sheathed cables in an insulated wall or above an insulated ceiling
- Cable laid directly in the insulation, no conduit
- One side touching a thermally conductive surface
SS 638 Table 4A, item 15
-
Sheathed cables in ducts or voids in the structure
- Method 4 when the void is no more than 5 Dₑ across, or its perimeter no more than 20 Dₑ
- Method 3 for larger voids
- Perimeter over 60 Dₑ: treat as an enclosed trench (R2–R4)
- For a group of cables, Dₑ is the sum of their diameters
SS 638 Table 4A, item 16
Trench R1–R4
-
Cables on the wall of an open or ventilated trench
- Fixed to the trench wall with the spacing of Method 12 or 13
SS 638 Table 4A, item 17
-
Enclosed trench, 450 mm wide × 300 mm deep or more
- Depth includes a 100 mm cover
- Two single cores one diameter apart, or three in trefoil touching
- Multicores 50 mm apart
- Apply the enclosed-trench rating factors (Table 4B3)
SS 638 Table 4A, item 18
-
Enclosed trench, 450 mm wide × 600 mm deep or more
- Depth includes a 100 mm cover
- Single cores in flat groups of two or three on the wall, one diameter apart, groups 50 mm apart
- Multicores 75 mm apart
- All cables at least 25 mm off the wall; apply Table 4B3 factors
SS 638 Table 4A, item 19
-
Enclosed trench, 600 mm wide × 760 mm deep or more
- Depth includes a 100 mm cover
- Single cores in flat groups or trefoil, groups 50 mm apart
- Multicores 75 mm apart
- All cables at least 25 mm off the wall; apply Table 4B3 factors
SS 638 Table 4A, item 20
Guide only, based on SS 638:2018 Table 4A. Cable selection and sizing should be confirmed by a qualified electrical engineer.