Aristoncavi URSUS® MT TUNNEL I PLUS – FG7H1OARAristoncavi

Aristoncavi · Distribution / Power feed

Aristoncavi URSUS® MT TUNNEL I PLUS – FG7H1OAR

Flame retardant
IEC 60332-1-2

About Aristoncavi URSUS® MT TUNNEL I PLUS – FG7H1OAR

URSUS® MT TUNNEL I PLUS – FG7H1OAR — Flexible cable for energy supply of MV equipment, in tunnelling and underground mining applications, according to IEC 60502-2 Standard.

Manufactured in Italy by Aristoncavi. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for conductor sizes, drum lengths, certification and lead time.

Construction
Phase Conductors
Conductor material: Bare copper
Conductor construction: class 5, according to IEC 60228
Insulation material: HEPR, G7 quality
Semiconductive layers: semiconductive tape over the conductor and inner and outer semiconductive rubber layer on the insulation
Protec. Earth Conductors
Material: Bare copper
Construction: individual copper wire screen
Control Conductors
Nominal cross section: 2,5 mm²
Conductor material: tinned copper
Conductor construction: class 5, according to IEC 60228
Insulation material: rubber compound
Central Filler
Material: rubber compound on textile polyester support
Cores Assembly
Assembly: twisted cores
Separator on the twisted assembly: TNT tape wound on the twisted cores
Inner Sheath
Sheath material: PVC, Rz quality
Armor
Material: steel wire braid
Assembly: braid over the inner sheath
Outer Sheath
Material: PVC, Rz quality
Colour: Red
Note
Upon request: URSUS® MT TUNNEL I ATOX PLUS: special version with LSOH outer sheath.
Electrical
Nominal rated voltage U₀/U (kV)
3,6/6 / 6/10 / 8,7/15 / 12/20
Test voltage (kV)
12,5 / 21 / 30,5 / 42
Max AC voltage (kV)
4,2/7,2 / 6,9/12 / 10,4/18 / 13,9/24
Electrical field control
inner and outer semiconductive layers extruded in a single pass with the insulation and the screen over every conductor
Current rating (A)
according to VDE 0298 Part 4
Thermal and mechanical
Maximum short circuit temperature (°C)
250
Maximum working temp. on the conductor (°C)
90
Ambient temperature: mobile condition (°C)
+ 5 to + 80
Ambient temperature: static condition (°C)
- 40 to + 80
Bending radius (mm)
according to VDE 0298 Part 3
Maximum tensile load (N/mm²)
15
Note
Referred to the total phase conductors cross section
Resistance
Burning behaviour
Flame retardant according to IEC 60332-1-2, EN 60332-1-2
Weather resistance
For indoor and outdoor application
Standards and compliance
Design standard
IEC 60502-2
Flame retardant
IEC 60332-1-2
Source
Aristoncavi mining & tunnelling catalogue, 02/2013