Aristoncavi URSUS® MT MIN PUR HF PLUS – (N)TSCGEWÖUAristoncavi

Aristoncavi · Mining

Aristoncavi URSUS® MT MIN PUR HF PLUS – (N)TSCGEWÖU

Flame retardant
IEC 60332-1-2 Halogen free according to IEC 60754-1 and IEC 60754-2

Type approvals and certificates

About Aristoncavi URSUS® MT MIN PUR HF PLUS – (N)TSCGEWÖU

URSUS® MT MIN PUR HF PLUS – (N)TSCGEWÖU — Flexible cable for energy supply of heavy mobile equipment such as drag lines, shovels, dredges, drills, uer extreme mechanical stresses and abrasion during trailing operation in opencast mine. Halogen free polyurethane sheathed version.

Manufactured in Italy by Aristoncavi. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for conductor sizes, drum lengths, certification and lead time.

Construction
Phase Conductors
Conductor material: tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)*
Insulation material: 3GI3 quality rubber compound, according to VDE 0207 Part 20
Semiconductive layers: semiconductive tape over the conductor and inner and outer semiconductive rubber layer on the insulation
Earth Conductors
Conductor material: tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)*
Covering material: semiconductive layer
Central Filler
Material: semiconductive compound on textile polyester support
Cores Assembly
Assembly: twisted cores with earth conductor split into 3 parts
Separator on the twisted assembly: Semiconductive tape wound on the twisted cores
Inner Sheath
Material: Halogen free polyurethane
Antitwisting element
Material: Polyester braid between inner and outer sheath
Outer Sheath
Material: Halogen free polyurethane
Colour: Yellow
Note
* Special construction for higher flexibility Upon request: URSUS® MT MIN PUR HF RFB special version with reflecting tape and transparent outer sheath, without textile braid.
Electrical
Nominal rated voltage U₀/U (kV)
3,6/6 / 6/10 / 8,7/15 / 12/20
Test voltage (kV)
11 / 17 / 24 / 29
Max AC voltage (kV)
4,2/7,2 / 6,9/12 / 10,4/18 / 13,9/24
Electrical field control
inner and outer semiconductive layers extruded in a single pass with the insulation
Current rating (A)
according to VDE 0298 Part 4
Thermal and mechanical
Maximum short circuit temperature (°C)
250
Maximum working temp. on the conductor (°C)
90
Ambient temperature: mobile condition (°C)
- 25 to + 80
Ambient temperature: static condition (°C)
- 50 to + 80
Bending radius (mm)
according to VDE 0298 Part 3
Maximum torsional stress (°/m)
± 25
Maximum tensile load (N/mm²)
20
Special test
Reeling test
Note
Referred to the total phase conductors cross section
Resistance
Burning behaviour
Flame retardant according to IEC 60332-1-2 Halogen free according to IEC 60754-1 and IEC 60754-2
Resistance to oil
According to IEC 60811-2-1
Ozone resistance
According to IEC 60811-2-1
Weather resistance
For indoor and outdoor application
Standards and compliance
Design standard
DIN VDE 0250 Part 813
Flame retardant
IEC 60332-1-2 Halogen free according to IEC 60754-1 and IEC 60754-2
Source
Aristoncavi mining & tunnelling catalogue, 02/2013