Aristoncavi URSUS® MT MIN F PLUS (N)TSCGEWÖU

Flame retardant
IEC 60332-1-2

Type approvals and certificates

About Aristoncavi URSUS® MT MIN F PLUS (N)TSCGEWÖU

URSUS® MT MIN F PLUS (N)TSCGEWÖU — Flexible cable for fixed energy distribution lines in mines and alongside material handling equipment.

Manufactured in Italy by Aristoncavi. Supplied and held in Singapore for delivery across ASEAN by Everwell Cables & Electrical (S.E.A.) Pte Ltd. Contact us for conductor sizes, drum lengths, certification and lead time.

Construction
Phase Conductors
Conductor material: Tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)
Insulation material: 3GI3 quality rubber compound, according to VDE 0207 Part 20
Semiconductive layers: semiconductive tape over the conductor and inner and outer semiconductive rubber layer on the insulation
Earth Conductors
Conductor material: Tinned copper
Conductor construction: class 5 VDE 0295 (IEC 60228)
Covering material: semiconductive layer
Central Filler
Material: semiconductive compound on textile polyester support
Cores Assembly
Assembly: twisted cores with earth conductor split into 3 parts
Separator on the twisted assembly: Semiconductive tape wound on the twisted cores
Inner Sheath
Material: rubber compound GM1b quality, according to VDE 0207 Part 21
Thickness: according to VDE 0250 Part 813 (table 2)
Outer Sheath
Material: rubber compound 5GM3 quality, according to VDE 0207 Part 21
Thickness: according to VDE 0250 Part 813 (table 2)
Colour: Red
Electrical
Nominal rated voltage U₀/U (kV)
3,6/6 / 6/10 / 8,7/15 / 12/20
Test voltage (kV)
11 / 17 / 24 / 29
Max AC voltage (kV)
4,2/7,2 / 6,9/12 / 10,4/18 / 13,9/24
Electrical field control
inner and outer semiconductive layers extruded in a single pass with the insulation
Current rating (A)
according to VDE 0298 Part 4
Thermal and mechanical
Maximum short circuit temperature (°C)
250
Maximum working temp. on the conductor (°C)
90
Ambient temperature: static condition (°C)
- 40 to + 80
Bending radius (mm)
according to VDE 0298 Part 3
Maximum tensile load (N/mm²)
20
Note
Referred to the total phase conductors cross section
Resistance
Burning behaviour
Flame retardant according to IEC 60332-1-2
Resistance to oil
According to IEC 60811-2-1
Ozone resistance
According to IEC 60811-2-1
Behaviour in water
According to HD22.16
Weather resistance
For indoor and outdoor application
Standards and compliance
Design standard
DIN VDE 0250 Part 813
Flame retardant
IEC 60332-1-2
Source
Aristoncavi mining & tunnelling catalogue, 02/2013